Új hozzászólás Aktív témák

  • xeri

    tag

    válasz lajos001 #708 üzenetére

    Szerintem erre gondolsz:

    5.5 Option switches
    The UPS has a set of four DIP switches on the rear panel which allow you
    to configure several options (see Secs. 5.5.1–5.5.4).
    0 (off) I (on)
    1
    2
    3
    4
    Note: You can set option switches at any time, and the effect is immediate.
    Note: If all of the option switches are set to the on position, the option switches are
    disabled. However, the functions controlled by the option switches are still
    available using UPS monitoring software (see Sec. 5.6.4).
    5.5.1 Option Switch 1
    The UPS contains utility fault detection circuitry that is extremely sensitive
    to line voltage distortions including spikes, notches, sudden dips, and
    swells. The UPS is factory-set to react to such line voltage distortions by
    immediately transferring the load to on-battery operation, affording
    maximum protection for all load types. Where power quality is poor
    because of local cyclic heavy load-switching, or the use of inexpensive fuel
    generators, the UPS may frequently transfer to on-battery. If the UPS is
    powering loads that operate normally under such conditions, battery
    capacity may be spent unnecessarily.
    Setting Option Switch 1 to the on ( I ) position desensitizes the UPS to rapid
    low-amplitude line-voltage fluctuations, and increases the UPS’s upper
    transfer voltage by 3%, for a total of 13% above the nominal input voltage.
    This helps maintain maximum battery capacity for major utility failures.
    20
    5.5.2 Option Switch 2
    Option Switch 2 functions differently for different versions of the UPS.
    n 100 Vac version
    No function; not used.
    n 120 Vac version
    The UPS’s factory-set input voltage limits for on-line and SmartBoost
    operation are centered on the nominal input voltage of 120 Vac (see also
    Sec. 9.1). When Option Switch 2 is set to the on ( I ) position, the upper and
    lower transfer voltages are lowered by 4% and centered on a nominal input
    of 115 Vac. This is useful where nominal input voltage is 110 to 115 Vac.
    n 220/230/240 Vac version
    The UPS’s factory-set on-battery output voltage and input voltage limits for
    on-line and SmartBoost operation are designed for use in regions where the
    nominal line voltage is 220 to 230 Vac. When Option Switch 2 is set to the
    on ( I ) position, the upper and lower transfer voltages are raised by 4% and
    centered on a nominal input of 240 Vac. In addition, the on-battery output
    voltage is increased to 240 Vac.
    5.5.3 Option Switch 3
    When Option Switch 3 is set to the on ( I ) position, the UPS’s audible alarm
    is disabled for the first 30 seconds of on-battery operation. This function is
    useful where brief power interruptions are frequent and cause the alarm to
    become annoying.
    5.5.4 Option Switch 4
    When Option Switch 4 is set to the on ( I ) position, the UPS’s low-battery
    alarm interval is extended from 2 minutes (factory setting) to 5 minutes.
    This function is useful if the UPS is protecting a computer system that
    requires more than 2 minutes warning to perform a graceful shutdown.
    Az idézet innen való, érdemes friss tulajdonosként átböngészned: [link]

Új hozzászólás Aktív témák